Logging data with hysteresis and timeout deadband reached

If Signalvalue has to be logged when:

  • Change of value is at least +- 1

  • When deadband timeout is reached and value hasn’t changed

The optimal solution:

  • Use Logging hyteresis at signal change

  • Create additional vchannel script for detecting deadband timeout

Example

Example signal name : Buffer 1 (Setpoint1)

Step 1

Set logging hysteresis in WEBfactoryStudio for signal „Buffer 1“ to 1 (or any other desired value)

Setting hysteresis in WEBfactoryStudio

Step 2

Set logging parameters in WEBfactoryStudio for signal „Buffer1“ to Log Mode „OnChange“ (Log Conditions).

Setting the Log Contidions for the Buffer1 signal

Step 3
  • Create VChannel signal with name e.g. „Buffer1Timeout“. Set Input Trigger for VChannel e.g. signal “Local Second” or “Local Hour”

  • Create VChannel Script as following:

Sub GetResult()
   
'To avoid unneccessary triggering of the VChannel it is recommended to use the MODULO value of the 'trigger signal

    ' If ((X(1) Mod 5) = 0) Then

        Dim signalName              'Signalname of Log Item
        Dim logGUID                 'GUID of Log-Tags or name of Logging Tabelle
        Dim deathBandTimeSpan       'timespan for Timeout deadband
        Dim diffUTCLocalTime        'difference between UTC time and local time in seconds
        Dim currentSignalValue
        Dim res
 
        signalName = "Buffer 1"
        logGUID = "L_8D9998A3D1464A829AB07AE516D7C06A"
        diffUTCLocalTime = -7200
        deathBandTimeSpan = 5
        currentSignalValue = ReadSignal(signalName)  'get actual signal value
         
        res = CheckDeathBand(currentSignalValue, logGUID, deathBandTimeSpan, diffUTCLocalTime)
        Result = res
    ' End If
End Sub

Setting up the VChannel

Hint: please modify the above parameters depending on your personal needs. The GUID for the LogTag can be read from SQL server by using SQL Management Studio. The WEBfactory server has to be started at least one time to force the WEBfactory server generating the Log GUID

Step 4
  • Create function „CheckDeathBand“ in VChannel script library to have the function reusable

  • The function is built as following:

'Function CheckDeathBand (currentSignalValue, logGUID, deathBandTimeSpan, diffUTCLocalTime) 

Dim cnnString
Dim sqlString
Dim ts
Dim result
 
    cnnString= DSN ' Connection String
    sqlString = "SELECT max([LoggingTime]) as MaxLoggingTime FROM [" & logGUID & "]"
 
    Set cn = CreateObject("ADODB.Connection")
    cn.Open cnnString       
 
    Set rs = CreateObject("ADODB.Recordset")
    rs.Open sqlString, cn, 0, 1
 
    If not rs.eof Then 
        If rs.fields("MaxLoggingTime").actualsize > 0 Then
            ts=cdate(rs.fields("MaxLoggingTime").value)
        End If
    end if
 
    rs.close
    Set rs = nothing
 
'check for last log entry is older than 5 seconds. (use h for hours)       
    If (datediff("s", ts, now()) + diffUTCLocalTime) > 5 Then	 
 
' create log entry when timeout is reached	
        cn.Execute  "INSERT INTO " & logGUID & " (LoggingTime,LoggingValue) VALUES (GETUTCDATE()," & replace(cstr(currentSignalValue), ",","." )  & ")"	
        result =  now() 
    Else
' if timeout is not reached just return last log timestamp
        result = ts
    End If
 
    cn.Close
    Set cn = nothing
 
    CheckDeathBand = result

'End Function

Creating the CheckDeathBand function

For additional log signals, the steps 1 – 3 have to be repeated and the variables have to be adapted.